192 Parameters
28.24 Constant frequency
sel3
When bit 0 of parameter 28.21 Constant frequency
function is 0 (Separate), selects a source that activates
constant frequency 3.
When bit 0 of parameter 28.21 Constant frequency
function is 1 (Packed), this parameter and parameters
28.22 Constant frequency sel1 and 28.23 Constant
frequency sel2 select three sources that are used to
activate constant frequencies. See table at parameter
28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant
frequency sel1.
Always off
28.26 Constant frequency 1 Defines constant frequency 1 (the frequency the motor will
turn when constant frequency 1 is selected).
5.00 Hz
-500.00…500.00 Hz Constant frequency 1. See par.
46.02
28.27 Constant frequency 2 Defines constant frequency 2. 10.00 Hz
-500.00…500.00 Hz Constant frequency 2. See par.
46.02
28.28 Constant frequency 3 Defines constant frequency 3. 15.00 Hz
-500.00…500.00 Hz Constant frequency 3. See par.
46.02
28.29 Constant frequency 4 Defines constant frequency 4. 20.00 Hz
-500.00…500.00 Hz Constant frequency 4. See par.
46.02
28.30 Constant frequency 5 Defines constant frequency 5. 25.00 Hz
-500.00…500.00 Hz Constant frequency 5. See par.
46.02
28.31 Constant frequency 6 Defines constant frequency 6. 40.00 Hz
-500.00…500.00 Hz Constant frequency 6. See par.
46.02
28.32 Constant frequency 7 Defines constant frequency 7. 50.00 Hz
-500.00…500.00 Hz Constant frequency 7. See par.
46.02
28.41 Frequency ref safe Defines a safe frequency reference value that is used with
supervision functions such as
12.03 AI supervision function
49.05 Communication loss action.
0.00 Hz
-500.00…500.00 Hz Safe frequency reference. See par.
46.02
28.42 Jogging 1 frequency
ref
Defines the frequency reference for jogging function 1 in
scalar control mode.
0.00Hz
-500.00…500.00 Hz Jogging 1 frequency reference. See par.
46.02
28.43 Jogging 2 frequency
ref
Defines the frequency reference for jogging function 2 in
scalar control mode.
0.00Hz
-500.00…500.00 Hz Jogging 2 frequency reference. See par.
46.02
No. Name/Value Description Default
FbEq 16
ACS180 FW.book Page 192 Tuesday, March 9, 2021 2:25 PM