Parameters 217
32.20 Supervision 2 high Defines the upper limit for signal supervision 2. 0.00
-21474830.00…
21474830.00
Upper limit. -
32.21 Supervision 2
hysteresis
Defines the hysteresis for the signal monitored by signal
supervision 2.
Note: This parameter applies to all selections of
parameter 32.15, not just Hysteresis.
0.00
0.00…100000.00 Hysteresis. -
32.25 Supervision 3 function Selects the mode of signal supervision function 3.
Determines how the monitored signal (see parameter
32.27) is compared to its lower and upper limits (32.29
and 32.30 respectively). The action to be taken when the
condition is fulfilled is selected by 32.26.
Disabled
Disabled Signal supervision 3 not in use. 0
Low Action is taken whenever the signal falls below its lower
limit.
1
High Action is taken whenever the signal rises above its upper
limit.
2
Abs low Action is taken whenever the absolute value of the signal
falls below its (absolute) lower limit.
3
Abs high Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both Action is taken whenever the signal falls below its low limit
or rises above its high limit.
5
Abs both Action is taken whenever the absolute value of the signal
falls below its (absolute) low limit or rises above its
(absolute) high limit.
6
Hysteresis Action is taken whenever the signal rises above the value
defined by the high limit + 0.5 · hysteresis range (32.31
Supervision 3 hysteresis). The action is deactivated when
the signal falls below the value defined by the low limit -
0.5 · hysteresis range.
7
32.26 Supervision 3 action Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 3
exceeds its limits.
Note: This parameter does not affect the status indicated
by 32.01 Supervision status.
No action
No action No warning or fault generated. 0
Warning Warning A8B0 Signal supervision is generated. 1
Fault The drive trips on fault 80B0 Signal supervision.2
Fault if running The drive trips on fault 80B0 Signal supervision if running. 3
32.27 Supervision 3 signal Selects the signal to be monitored by signal supervision
function 3.
For the available selections, see parameter 32.07
Supervision 1 signal.
Tor que
32.28 Supervision 3 filter
time
Defines a filter time constant for the signal monitored by
signal supervision 3.
0.000 s
0.000 30.000 s Signal filter time. 1000 = 1 s