346 Fault tracing
0011 Program too large. Remove blocks until the error stops.
0012 Program is empty. Correct the program and download it to
the drive.
001C A non-existing parameter or
block is used in the parameter.
Edit the program to correct the parameter
reference, or use an existing block.
001E Output to parameter failed
because the parameter was
write-protected.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
0023 Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
0024 Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
Other - Contact your local ABB representative,
quoting the auxiliary code.
64B2 User set fault Loading of user parameter set
failed because
requested set does not exist
set is not compatible with
control program
drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1 Kernel overload Operating system error. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6581 Parameter system Parameter load or save failed. Try forcing a save using parameter 96.07
Parameter save manually. Retry.
6681 EFB comm loss
Programmable fault: 58.14
Communication loss
action
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the EIA-485
terminals 25, 26, 27 and 28 on the
control unit.
6682 EFB config file Embedded fieldbus (EFB)
configuration file could not be
read.
Contact your local ABB representative.
6683 EFB invalid
parameterization
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Check the settings in parameter group 58
Embedded fieldbus.
6684 EFB load fault Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Contact your local ABB representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6685 EFB fault 2 Fault reserved for the EFB
protocol application.
Check the documentation of the protocol.
6686 EFB fault 3 Fault reserved for the EFB
protocol application.
Check the documentation of the protocol.
Code
(hex)
Fault / Aux. code Cause What to do
ACS180 FW.book Page 346 Tuesday, March 9, 2021 2:25 PM