X1A
1 SCR Signal cable shield (screen)
2AI1 Output frequency reference: 0…10 V
3 GND Analog input circuit common
4 +10V Reference voltage: +10 V DC, max. 10 mA
5 AI2 Not in use by default. 0…10 V
6 GND Analog input circuit common
7AO Output frequency value: 0…20 mA
8 GND Analog output circuit common
9 +24V Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND Auxiliary voltage output common
11 DCOM Digital input common
12 DI1 Stop (0) / Start (1)
13 DI2 Forward (0) / Reverse (1)
14 DI3 Constant speed selection
1)
15 DI4 Constant speed selection
1)
16 DI5 Acceleration and deceleration selection
2)
X1B
17 ROCOM Relay output 1
No fault [Fault (-1)]
18 RONC
19 RONO
20 DOSRC Digital output, max. 100 mA
No fault [Fault (-1)]
21 DOOUT
22 DOGND
max. 500 ohm
1…10 kohm
3)
1)
See parameter group 12 CONSTANT
SPEEDS:
2)
0 = ramp times according to parameters
2202 and 2203.
1 = ramp times according to parameters
2205 and 2206.
3)
360 degree grounding under a clamp.
Tightening torque: 0.4 N·m (3.5 lbf·in).