Actual signals and parameters 257
DONE Reset not requested (normal operation). 0
RESET Reset energy counters, The value reverts automatically to
DONE.
1
46 PUMP CLEANING Set-up of pump cleaning.
4601 PUMP CLEAN
TRIG
Defines how the Pump cleaning function is triggered. The
pump cleaning sequence consists of forward and reverse
“steps”.
WARNING! Before enabling the Pump cleaning
function, ensure it is safe to perform the pump cleaning
sequence with the connected equipment.
Notes:
The Pump cleaning function overrides parameter 1003
DIRECTION.
The Pump cleaning function observes the maximum forward
and reverse frequencies (parameters 2007 MINIMUM
FREQ and 2008 MAXIMUM FREQ).
The Pump cleaning function always uses acceleration time
2 (parameter 2205) and deceleration time 2 (parameter
2206).
The drive must be ready and its Run enable signal must be
present before the pump cleaning sequence can start.
NOT SEL
NOT SEL No triggering source defined. 0
DI1 Trigger on the rising edge of digital input DI1 1
DI2 See selection DI1.2
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
DI1/SUP1OVR Enable on the rising edge of digital input DI1 or SUPRV1
OVER (parameter 1401 RELAY OUTPUT 1). See
parameter group 32 SUPERVISION.
7
DI2/SUP1OVR See selection DI1/SUP1OVR.8
DI3/SUP1OVR See selection DI1/SUP1OVR.9
DI4/SUP1OVR See selection DI1/SUP1OVR.10
DI5/SUP1OVR See selection DI1/SUP1OVR.11
All parameters
No. Name/Value Description Def/FbEq
t
Forward
Reverse
4607 46044605 4606 4604 4605 4604
4603
4602
4608