230 Actual signals and parameters
DI5 Digital input DI5. Used when parameter 3501 SENSOR
TYPE value is set to THERM(0)/THERM(1).
7
3503 ALARM LIMIT Defines the alarm limit for motor temperature measurement.
Alarm MOTOR TEMP indication is given when the limit is
exceeded. When parameter 3501 SENSOR TYPE value is
set to THERM(0)/THERM(1): 1 = alarm.
0
x…x Alarm limit -
3504 FAULT LIMIT Defines the fault trip limit for motor temperature
measurement. The drive trips on fault MOT OVERTEMP
when the limit is exceeded. When parameter 3501
SENSOR TYPE value is set to THERM(0)/THERM(1): 1 =
fault.
0
x…x Fault limit -
3505 AO
EXCITATION
Enables current feed from analog output AO. Parameter
setting overrides parameter group 15 ANALOG OUTPUTS
settings.
With PTC the output current is 1.6 mA.
With Pt100 the output current is 9.1 mA.
DISABLE
DISABLE Disabled 0
ENABLE Enabled 1
36 TIMED
FUNCTIONS
Time periods 1 to 4 and booster signal. See section Timed
functions on page 147.
3601 TIMERS
ENABLE
Selects the source for the timed function enable signal. NOT SEL
NOT SEL Timed function is not selected. 0
DI1 Digital input DI. Timed function enable on the rising edge of
DI1.
1
DI2 See selection DI1.2
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
ACTIVE Timed function is always enabled. 7
DI1 CMODE Timed function enable on the rising edge of DI1. Timed
function is in continuous mode, in which the start date can
be different from the stop date.
11
DI2 CMODE See selection DI1 CMODE.12
DI3 CMODE See selection DI1 CMODE.13
DI4 CMODE See selection DI1 CMODE.14
DI5 CMODE See selection DI1 CMODE.15
CONT MODE Timed function enabled in continuous mode, in which the
start date can be different from the stop date.
17
DI1(INV) Inverted digital input DI1. Timed function enable on the
falling edge of DI1.
-1
DI2(INV) See selection DI1(INV).-2
DI3(INV) See selection DI1(INV).-3
DI4(INV) See selection DI1(INV).-4
All parameters
No. Name/Value Description Def/FbEq