Actual signals and parameters   167
Actual signals in the short parameter view
Parameters in the short parameter view
Actual signals in the short parameter view 
No. Name/Value Description FbEq
04 FAULT HISTORY Fault history (read-only). See group 04 FAULT HISTORY in 
the list of all parameters. 
0401 LAST FAULT Code of the latest fault.  1 = 1
Parameters in the short parameter view
No. Name/Value Description Def/FbEq
11 REFERENCE 
SELECT
Panel reference type, external control location selection and 
external reference sources and limits. See group 11 
REFERENCE SELECT in the list of all parameters. 
1105 REF1 MAX Defines the maximum value for external reference REF1. E: 50.0 Hz
U: 60.0 Hz
12 CONSTANT 
SPEEDS
Constant speed (drive output frequency) selection and 
values. See group 12 CONSTANT SPEEDS in the list of all 
parameters. 
1202 CONST 
SPEED 1
Defines constant drive output frequency 1. E: 5.0 Hz
U: 6.0 Hz
1203 CONST 
SPEED 2
Defines constant drive output frequency 2. E: 10.0 Hz 
U: 12.0 Hz
1204 CONST 
SPEED 3
Defines constant drive output frequency 3. E: 15.0 Hz 
U: 18.0 Hz
13 ANALOG INPUTS Analog input signal processing. See group 13 ANALOG 
INPUTS in the list of all parameters.
1301 MINIMUM AI1 Defines the minimum %-value that corresponds to minimum 
mA/(V) signal for analog input AI1. 
1.0%
14 RELAY OUTPUTS Status information indicated through relay output, and relay 
operating delays. See group 14 RELAY OUTPUTS in the list 
of all parameters. 
1401 RELAY 
OUTPUT 1
Selects a drive status indicated through relay output RO 1. FAULT( -1)
16 SYSTEM 
CONTROLS
Parameter view, Run enable, parameter lock etc. See group 
16 SYSTEM CONTROLS in the list of all parameters. 
1611 PARAMETER 
VIEW
Selects the parameter view, ie which parameters are shown 
on the control panel.
SHORT 
VIEW
20 LIMITS Drive operation limits. See group 20 LIMITS in the list of all 
parameters. 
2008 MAXIMUM 
FREQ
Defines the maximum limit for the drive output frequency. E: 50.0 Hz
U: 60.0 Hz
21 START/STOP Start and stop modes of the motor. See group 21 
START/STOP in the list of all parameters.
2102 STOP 
FUNCTION
Selects the motor stop function. COAST