236   Actual signals and parameters
3717 LOAD TORQ 
LOW 5
Defines the torque value of the fifth underload curve 
definition point. Must be smaller than 3718 LOAD TORQ 
HIGH 5.
30%
0…600% Torque 1 = 1%
3718 LOAD TORQ 
HIGH 5
Defines the torque value of the fifth overload curve definition 
point
300%
0…600% Torque 1 = 1%
40 PROCESS PID 
SET 1
Process PID (PID1) control parameter set 1. See section 
PID control on page 138.
4001 GAIN Defines the gain for the process PID controller. High gain 
may cause speed oscillation.
1.0
0.1…100.0 Gain. When value is set to 0.1, the PID controller output 
changes one-tenth as much as the error value. When value 
is set to 100, the PID controller output changes one hundred 
times as much as the error value.
1 = 0.1
4002 INTEGRATION 
TIME
Defines the integration time for the process PID1 controller. 
The integration time defines the rate at which the controller 
output changes when the error value is constant. The 
shorter the integration time, the faster the continuous error 
value is corrected. Too short an integration time makes the 
control unstable.
60.0 s
0.0 = NOT SEL
0.1…3600.0 s
Integration time. If parameter value is set to zero, integration 
(I-part of the PID controller) is disabled.
1 = 0.1 s
All parameters
No. Name/Value Description Def/FbEq
t
A = Error
B = Error value step
C = Controller output with gain = 1 
D = Controller output with gain = 10
D (4001 = 10)
C (4001 = 1)
B
A
4002