Actual signals and parameters 247
4039 INT SETPNT
SEL
Selects the source for the selection of the internal setpoint
used as the process PID controller reference when
parameter 4010 SET POINT SEL value is set to INTERNAL.
Example:
4010 SET POINT SEL = INTERNAL
4039 INT SETPNT SEL = DI2
Digital input DI2 = 1
-
> 4036 INTERNAL SETPNT2 is used as the reference.
NOT SEL
NOT SEL 4011 INTERNAL SETPNT is used as the reference. 0
DI1 0 = 4011 INTERNAL SETPNT is used. 1 = 4036 INTERNAL
SETPNT2 is used.
1
DI2 See selection DI1.2
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
DI1,2 Selects with digital inputs DI1 and DI2 which internal
setpoint is used as the reference. 1 = DI active, 0 = DI
inactive.
7
DI2,3 See selection DI1,2.8
DI3,4 See selection DI1,2.9
DI4,5 See selection DI1,2.10
TIMED FUNC 1 0 = 4011 INTERNAL SETPNT is used. 1 = 4036 INTERNAL
SETPNT2 is used.
15
TIMED FUNC 2 See selection TIMED FUNC 1.16
TIMED FUNC 3 See selection TIMED FUNC 1.17
TIMED FUNC 4 See selection TIMED FUNC 1.18
TIMED
FUN1&2
Selects with timed functions 1 and 2 which internal setpoint
is used as the reference. 1 = timed function active,
0 = timed function inactive.
19
41 PROCESS PID
SET 2
Process PID (PID1) control parameter set 2. See section
PID control on page 138.
4101 GAIN See parameter 4001 GAIN.
4102 INTEGRATION
TIME
See parameter 4002 INTEGRATION TIME.
All parameters
No. Name/Value Description Def/FbEq
DI1 DI2 Internal setpoint selected
004011 INTERNAL SETPNT
104036 INTERNAL SETPNT2
014037 INTERNAL SETPNT3
114038 INTERNAL SETPNT4
Timed
function 1
Timed
function 2
Internal setpoint selected
004011 INTERNAL SETPNT
104036 INTERNAL SETPNT2
014037 INTERNAL SETPNT3
114038 INTERNAL SETPNT4