234   Actual signals and parameters
3629 TIMED FUNC 4 
SRC
See parameter 3626 TIMED FUNC 1 SRC.
See parameter 3626 TIMED FUNC 1 SRC.
3630 ALTERNATING 
TIMER 
Defines the time interval for the timer to switch between 
On (1)  and Off (0) states (starting from the On state), 
based on the selections ALTERNATING or ALT+BOOSTER 
in the timer source parameters 3626...3629.
• ALTERNATING: Alternating time period is enabled. The 
time periods T1, T2, T1+T2 and T3 are ignored, for the 
specific timed function.
• ALT+BOOSTER: Alternating time period and booster 
times are enabled simultaneously.
0.0 h
0.0...1000.0 h Time interval
37 USER LOAD 
CURVE
Defines supervision of a user adjustable load curve (motor 
torque as a function of frequency). The curve is defined by 
five points. See section User load curve on page 150.
3701 USER LOAD C 
MODE
Defines supervision mode for the user adjustable load 
curve.
NOT SEL
NOT SEL Supervision not active 0
UNDERLOAD Supervision for the torque dropping below the underload 
curve
1
OVERLOAD Supervision for the torque exceeding the overload curve 2
BOTH Supervision for the torque dropping below the underload 
curve or exceeding the overload curve
3
3702 USER LOAD C 
FUNC
Defines the action wanted during load supervision FAULT
FAULT A fault is generated when the condition defined by 3701 
USER LOAD C MODE has been valid longer than the time 
set by 3703 USER LOAD C TIME.
1
ALARM An alarm is generated when the condition defined by 3701 
USER LOAD C MODE has been valid longer than half of the 
time set by 3703 USER LOAD C TIME.
2
All parameters
No. Name/Value Description Def/FbEq
Overload area
Underload area
Allowed operating area
3706
Motor torque (%)
Output frequency (Hz)
3715
3714
3718
3717
3709
3712
3705
3711
3708
3704 3707 3710 3713 3716