Fieldbus control with the embedded fieldbus   289
Setting up communication through the embedded Modbus
Before configuring the drive for fieldbus control, install the fieldbus according to 
instructions given in section Connecting the embedded fieldbus on page 54. 
The communication through the fieldbus link is initialized by setting parameter 9802 
COMM PROT SEL to STD MODBUS or MODBUS RS232. The communication 
parameters in group 53 EFB PROTOCOL must also be adjusted. See the table 
below.
After the configuration parameters in group 53 EFB PROTOCOL have been set, the 
Drive control parameters on page 291 must be checked and adjusted when 
necessary.
Parameter Alternative 
settings
Setting for
fieldbus control
Function/Information
COMMUNICATION INITIALIZATION
9802 COMM PROT 
SEL
NOT SEL
STD MODBUS
MODBUS RS232
STD MODBUS 
(with EIA-485)
MODBUS RS232 
(with RS-232)
Initializes embedded fieldbus 
communication.
ADAPTER MODULE CONFIGURATION
1611 PARAMETER 
VIEW
FLASHDROP
SHORT VIEW
LONG VIEW
LONG VIEW Selects the long view.
5302 EFB STATION 
ID
0…65535 Any Defines the station ID address 
of the EIA-485/RS-232 link. No 
two stations on line may have 
the same address.
5303 EFB BAUD 
RATE
1.2 kbit/s
2.4 kbit/s
4.8 kbit/s
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
57.6 kbit/s
76.8 kbit/s
Defines the communication 
speed of the EIA-485/RS-232 
link.
5304 EFB PARITY 8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
Selects the parity setting. The 
same settings must be used in 
all on-line stations. 
5305 EFB CTRL 
PROFILE
ABB DRV LIM
DCU PROFILE
ABB DRV FULL
Any Selects the communication 
profile used by the drive. See 
section Communication 
profiles on page 302.
5310
…
5317 
EFB PAR 10
… 
EFB PAR 17
0…65535 Any Selects an actual value to be 
mapped to Modbus register 
400xx.