Technical data 345
Losses, cooling data and noise
Losses and cooling data
Frame size R0 has natural convection cooling. Frame sizes R1…R4 are provided
with an internal fan. The air flow direction is from bottom to top.
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O and panel not in use) and maximum load
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat
dissipation is the sum of the heat dissipation in the main and control circuits.
Type Heat dissipation Air flow
ACS310- Main circuit Control circuit
x = E/U
1)
Rated I
LD
Min Max
W BTU/Hr W BTU/Hr W BTU/Hr m
3
/h ft
3
/min
1-phase U
N
= 200…240 V (200, 208, 220, 230, 240 V)
01x-02A4-2 19 65 6.1 21 22.7 78 - -
01x-04A7-2 38 130 9.5 32 26.4 90 24 14
01x-06A7-2 60 205 9.5 32 26.4 90 24 14
01x-07A5-2 62 212 11 36 27.5 94 21 12
01x-09A8-2 83 283 11 36 27.5 94 21 12
3-phase U
N
= 200…240 V (200, 208, 220, 230, 240 V
03x-02A6-2 19 65 6.1 21 23 78 - -
03x-03A9-2 31 106 6.1 21 23 78 - -
03x-05A2-2 38 130 9.5 32 26 90 24 14
03x-07A4-2 60 205 9.5 32 26 90 24 14
03x-08A3-2 62 212 9.5 32 26 90 21 12
03x-10A8-2 83 283 11 36 28 94 21 12
03x-14A6-2 112 383 11 36 28 94 52 31
03x-19A4-2 152 519 11 36 28 94 52 31
03x-26A8-2 250 854 17 57 35 120 71 42
03x-34A1-2 270 922 33 110 58 200 96 57
03x-50A8-2 430 1469 33 110 58 200 96 57
3-phase U
N
= 380…480 V (380, 400, 415, 440, 460, 480 V)
03x-01A3-4 11 38 6.6 23 24 83 - -
03x-02A1-4 16 55 6.6 23 24 83 - -
03x-02A6-4 21 72 9.8 33 29 98 13 8
03x-03A6-4 31 106 9.8 33 29 98 13 8
03x-04A5-4 40 137 9.8 33 29 98 13 8
03x-06A2-4 61 208 9.8 33 29 98 19 11
03x-08A0-4 74 253 14 48 33 110 24 14
03x-09A7-4 94 321 14 48 33 110 24 14