Start-up and control with I/O 57
8
Start-up and control with I/O
What this chapter contains
The chapter tells how to:
perform the start-up
start, stop, change the direction of the motor rotation and adjust the speed of the
motor through the I/O interface
Using the control panel to do these tasks is explained briefly in this chapter. For
details on how to use the control panel, refer to chapter Control panels on page 67.
How to start up the drive
WARNING! The start-up may only be carried out by a qualified
electrician.
The safety instructions given in chapter Safety on page 15 must be followed during
the start-up procedure.
The drive starts up automatically at power up if the external run command is on and
the drive is in the remote control mode.
Check that the starting of the motor does not cause any danger. De-couple the
driven machine if there is a risk of damage in case of incorrect direction of rotation.
Note: By default, parameter 1611 PARAMETER VIEW is set to 2 (SHORT VIEW),
and you cannot see all actual signals and parameters. To be able to view them, set
parameter 1611 PARAMETER VIEW to 3 (LONG VIEW).