168 Actual signals and parameters
22 ACCEL/DECEL Acceleration and deceleration times. See group 22
ACCEL/DECEL in the list of all parameters.
2202 ACCELER
TIME 1
Defines the acceleration time 1. 5.0 s
2203 DECELER
TIME 1
Defines the deceleration time 1. 5.0 s
53 EFB PROTOCOL Embedded fieldbus link settings. See chapter Fieldbus
control with the embedded fieldbus on page 287.
5301 EFB
PROTOCOL ID
Contains the identification and program version of the
protocol.
Note: You can reset this parameter only with parameter
9802 COMM PROT SEL.
-
5302 EFB STATION
ID
Defines the address of the device. Two units with the same
address are not allowed on-line.
1
5303 EFB BAUD
RATE
Defines the transfer rate of the link 9.6 kbit/s
5304 EFB PARITY Defines the use of parity and stop bit(s) and the data length.
The same setting must be used in all on-line stations.
8 NONE 1
5305 EFB CTRL
PROFILE
Selects the communication profile. See section
Communication profiles on page 302.
ABB DRV
LIM
5306 EFB OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
5307 EFB CRC
MESSAGES
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note: High electromagnetic noise levels generate errors.
0
5308 EFB UART
ERRORS
Number of messages with a character error received by the
drive.
0
5309 EFB STATUS Status of the EFB protocol. IDLE
5310 EFB PAR 10 Selects an actual value to be mapped to Modbus register
40005.
0
5311 EFB PAR 11 Selects an actual value to be mapped to Modbus register
40006.
0
5312 EFB PAR 12 Selects an actual value to be mapped to Modbus register
40007.
0
5313 EFB PAR 13 Selects an actual value to be mapped to Modbus register
40008.
0
5314 EFB PAR 14 Selects an actual value to be mapped to Modbus register
40009.
0
5315 EFB PAR 15 Selects an actual value to be mapped to Modbus register
40010.
0
5316 EFB PAR 16 Selects an actual value to be mapped to Modbus register
40011.
0
5317 EFB PAR 17 Selects an actual value to be mapped to Modbus register
40012.
0
5318 EFB PAR 18 For Modbus: Sets an additional delay before the drive
begins transmitting response to the master request.
0
Parameters in the short parameter view
No. Name/Value Description Def/FbEq