EasyManua.ls Logo

ABB ACS310 - Options; Start-Up Data

ABB ACS310
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Actual signals and parameters 283
8127 MOTORS Sets the actual number of PFC controlled motors (maximum
7 motors: 1 speed regulated, 3 connected direct-on-line and
3 spare motors).
This value includes also the speed regulated motor.
This value must be compatible with the number of relays
allocated to PFC if the Autochange function is used.
If Autochange function is not used, the speed regulated
motor does not need to have a relay output allocated to PFC
but it needs to be included in this value.
2
1…7 Number of PFC motors 1 = 1
8128 AUX START
ORDER
Sets the start order of the auxiliary motors. EVEN
RUNTIME
EVEN
RUNTIME
Time sharing is active. Evens out the cumulative run time of
the auxiliary motors. The start order depends on the run
times: The auxiliary motor whose cumulative run time is
shortest is started first, then the motor whose cumulative
run time is the second shortest etc. When the demand
drops, the first motor to be stopped is the one whose
cumulative run time is longest.
1
RELAY
ORDER
The start order is fixed to be the order of the relays. 2
98 OPTIONS External serial communication activation
9802 COMM PROT
SEL
Activates the external serial communication and selects the
interface.
Note: Before activating embedded fieldbus communication,
set parameter 1611 PARAMETER VIEW to LONG VIEW
(3).
STD
MODBUS
NOT SEL No communication 0
STD MODBUS Embedded fieldbus, EIA-485 interface (I/O terminals
23…26). See chapter Fieldbus control with the embedded
fieldbus on page 287.
1
MODBUS
RS232
Embedded fieldbus. Interface: RS-232 (ie control panel
connector). See chapter Fieldbus control with the
embedded fieldbus on page 287.
10
99 START-UP DATA Language selection. Definition of motor set-up data.
9901 LANGUAGE Selects the display language used on the Assistant control
panel.
Note: With the ACS-CP-D Assistant control panel, the
following languages are available: English (0), Chinese (1),
Korean (2) and Japanese (3).
ENGLISH
ENGLISH British English 0
ENGLISH (AM) American English 1
DEUTSCH German 2
ITALIANO Italian 3
ESPAÑOL Spanish 4
PORTUGUES Portuguese 5
NEDERLANDS Dutch 6
FRANÇAIS French 7
DANSK Danish 8