Actual signals and parameters   283
8127 MOTORS Sets the actual number of PFC controlled motors (maximum 
7 motors: 1 speed regulated, 3 connected direct-on-line and 
3 spare motors).
This value includes also the speed regulated motor.
This value must be compatible with the number of relays 
allocated to PFC if the Autochange function is used.
If Autochange function is not used, the speed regulated 
motor does not need to have a relay output allocated to PFC 
but it needs to be included in this value.
2
1…7 Number of PFC motors 1 = 1
8128 AUX START 
ORDER
Sets the start order of the auxiliary motors. EVEN 
RUNTIME
EVEN 
RUNTIME
Time sharing is active. Evens out the cumulative run time of 
the auxiliary motors. The start order depends on the run 
times: The auxiliary motor whose cumulative run time is 
shortest is started first, then the motor whose cumulative 
run time is the second shortest etc. When the demand 
drops, the first motor to be stopped is the one whose 
cumulative run time is longest.
1
RELAY 
ORDER
The start order is fixed to be the order of the relays. 2
98 OPTIONS External serial communication activation
9802 COMM PROT 
SEL
Activates the external serial communication and selects the 
interface.
Note: Before activating embedded fieldbus communication, 
set parameter 1611 PARAMETER VIEW to LONG VIEW 
(3).
STD 
MODBUS
NOT SEL No communication 0
STD MODBUS Embedded fieldbus, EIA-485 interface (I/O terminals 
23…26). See chapter Fieldbus control with the embedded 
fieldbus on page 287.
1
MODBUS 
RS232
Embedded fieldbus. Interface: RS-232 (ie control panel 
connector). See chapter Fieldbus control with the 
embedded fieldbus on page 287.
10
99 START-UP DATA Language selection. Definition of motor set-up data.
9901 LANGUAGE Selects the display language used on the Assistant control 
panel.
Note: With the ACS-CP-D Assistant control panel, the 
following languages are available: English (0), Chinese (1), 
Korean (2) and Japanese (3).
ENGLISH
ENGLISH British English 0
ENGLISH (AM) American English 1
DEUTSCH German 2
ITALIANO Italian 3
ESPAÑOL Spanish 4
PORTUGUES Portuguese 5
NEDERLANDS Dutch 6
FRANÇAIS French 7
DANSK Danish 8
All parameters
No. Name/Value Description Def/FbEq