Actual signals and parameters 183
DI4U,5D(NC) See parameter 1103 REF1 SELECT.31
FREQ INPUT See parameter 1103 REF1 SELECT.32
1107 REF2 MIN Defines the minimum value for external reference REF2.
Corresponds to the minimum setting of the used source
signal.
0.0%
0.0…100.0% Value in percent of the maximum frequency / maximum
speed / nominal torque. See the example for parameter
1104 REF1 MIN for correspondence to the source signal
limits.
1 = 0.1%
1108 REF2 MAX Defines the maximum value for external reference REF2.
Corresponds to the maximum setting of the used source
signal.
100.0%
0.0…100.0% Value in percent of the maximum frequency / maximum
speed / nominal torque. See the example for parameter
1104 REF1 MIN for correspondence to the source signal
limits.
1 = 0.1%
12 CONSTANT
SPEEDS
Constant speed (drive output frequency) selection and
values. See section Constant speeds on page 131.
1201 CONST
SPEED SEL
Activates the constant speeds (drive output frequencies) or
selects the activation signal.
DI3,4
NOT SEL No constant speed in use 0
DI1 Speed defined by parameter 1202 CONST SPEED 1 is
activated through digital input DI1. 1 = active, 0 = inactive.
1
DI2 Speed defined by parameter 1202 CONST SPEED 1 is
activated through digital input DI2. 1 = active, 0 = inactive.
2
DI3 Speed defined by parameter 1202 CONST SPEED 1 is
activated through digital input DI3. 1 = active, 0 = inactive.
3
DI4 Speed defined by parameter 1202 CONST SPEED 1 is
activated through digital input DI4. 1 = active, 0 = inactive.
4
DI5 Speed defined by parameter 1202 CONST SPEED 1 is
activated through digital input DI5. 1 = active, 0 = inactive.
5
DI1,2 Constant speed selection through digital inputs DI1 and
DI2.1 = DI active, 0 = DI inactive.
7
DI2,3 See selection DI1,2.8
DI3,4 See selection DI1,2.9
DI4,5 See selection DI1,2.10
All parameters
No. Name/Value Description Def/FbEq
DI1 DI2 Operation
0 0 No constant speed
1 0 Speed defined by par. 1202 CONST SPEED 1
0 1 Speed defined by par. 1203 CONST SPEED 2
1 1 Speed defined by par. 1204 CONST SPEED 3