346 Technical data
Noise
Terminal and lead-through data for the power cables
03x-13A8-4 130 444 12 41 31 110 52 31
03x-17A2-4 173 591 12 41 31 110 52 31
03x-25A4-4 266 908 17 57 35 120 71 42
03x-34A1-4 350 1195 33 110 58 200 96 57
03x-41A8-4 440 1503 33 110 58 200 96 57
03x-48A4-4 530 1810 33 110 58 200 96 57
00578903.xls G
1)
E = EMC filter connected (metal EMC filter screw installed),
U = EMC filter disconnected (plastic EMC filter screw installed), U.S parameterization,
Frame
size
Noise level
dBA
R0 <30
R1 50…62
R2 50…62
R3 50…62
R4 <62
00578903.xls D
Frame
size
Max. cable
diameter for
NEMA 1
U1, V1, W1, U2, V2, W2 PE
U1, V1, W1,
U2, V2, W2
Max. terminal size
flexible/rigid
Tightening
torque
Max. clamp size
solid or stranded
Tightening
torque
mm in mm
2
AWG N·m lbf·in mm
2
AWG N·m lbin
R0 16 0.63 4.0/6.0 10 0.8 7 25 3 1.2 11
R1 16 0.63 4.0/6.0 10 0.8 7 25 3 1.2 11
R2 16 0.63 4.0/6.0 10 0.8 7 25 3 1.2 11
R3 29 1.14 10.0/16.0 6 1.7 15 25 3 1.2 11
R4 35 1.38 25.0/35.0 2 2.5 22 25 3 1.2 11
00578903.xls G
Type Heat dissipation Air flow
ACS310- Main circuit Control circuit
x = E/U
1)
Rated I
LD
Min Max
W BTU/Hr W BTU/Hr W BTU/Hr m
3
/h ft
3
/min
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182