Fieldbus control with the embedded fieldbus   307
 DCU communication profile
Because the DCU profile extends the control and status interface to 32 bits, two 
different signals are needed for both the control (0301 and 0302) and status (0303 
and 0304) words.
The following tables describe the Control word content for the DCU profile.
DCU profile Control word, parameter 0301 FB CMD WORD 1
Bit Name Value Information
0 STOP  1 Stop according to either the stop mode parameter (2102) or 
the stop mode requests (bits 7 and 8).
Note: Simultaneous STOP and START commands result in 
a stop command.
0 No operation
1START 1 Start
Note: Simultaneous STOP and START commands result in 
a stop command.
0 No operation
2 REVERSE 1 Reverse direction. The direction is defined by using the 
XOR operation on bit 2 and 31 (= sign of the reference) 
values.
0 Forward direction.
3 LOCAL 1 Enter the local control mode.
0 Enter external control mode.
4 RESET -> 1 Reset.
other No operation
5  EXT2 1 Switch to external control EXT2.
0 Switch to external control EXT1.
6 RUN_DISABLE 1 Activate Run disable.
0 Activate Run enable.
7 STPMODE_R 1 Stop along currently active deceleration ramp (bit 10). Bit 0 
value must be 1 (= STOP).
0 No operation
8 STPMODE_EM 1 Emergency stop. But does not cause an EMERGENCY 
STOP alarm.
Bit 0 value must be 1 (=STOP).
0 No operation
9 STPMODE_C 1 Coast to stop. Bit 0 value must be 1 (= STOP).
0 No operation
10 RAMP_2 1 Use acceleration/deceleration ramp pair 2 (defined by 
parameters 2205…2207).
0 Use acceleration/deceleration ramp pair 1 (defined by 
parameters 2202…2204).
11 RAMP_OUT_0 1 Force ramp output to zero.
0 No operation
12 RAMP_HOLD 1 Halt ramping (Ramp function generator output held).
0 No operation