200 Actual signals and parameters
2007 MINIMUM
FREQ
Defines the minimum limit for the drive output frequency.
A positive (or zero) minimum frequency value defines two
ranges, one positive and one negative.
A negative minimum frequency value defines one speed
range.
Note: MINIMUM FREQ <
MAXIMUM FREQ.
0.0 Hz
-500.0500.0 Hz Minimum frequency 1 = 0.1 Hz
2008 MAXIMUM
FREQ
Defines the maximum limit for the drive output frequency. E: 50.0 Hz
U: 60.0 Hz
0.0…500.0 Hz Maximum frequency 1 = 0.1 Hz
21 START/STOP Start and stop modes of the motor
2101 START
FUNCTION
Selects the motor starting method. AUTO
AUTO The drive starts the motor instantly from zero frequency. If
flying start is required, use selection SCAN START.
1
DC MAGN The drive pre-magnetizes the motor with DC current before
the start. The pre-magnetizing time is defined by parameter
2103 DC MAGN TIME.
Note: Starting the drive connected to a rotating motor is not
possible when DC MAGN is selected.
WARNING! The drive starts after the set pre-
magnetizing time has passed even if the motor
magnetization is not completed. In applications where a full
break-away torque is essential, always ensure that the
constant magnetizing time is long enough to allow
generation of full magnetization and torque.
2
All parameters
No. Name/Value Description Def/FbEq
2008
2007
0
f
2008 value is < 0
2007 value is > 0
f
2008
2007
0
-(2007)
-(2008)
t
t
Allowed
frequency range
Allowed
frequency range
Allowed
frequency range