Program features 125
Diagnostics
Programmable analog output
One programmable current output (0…20 mA) is available. Analog output signal can
be inverted, filtered and the maximum and minimum values can be adjusted. The
analog output signals can be proportional to motor speed, output frequency, output
current, motor torque, motor power, etc. The update cycle for the analog output is
2ms.
It is also possible to write a value to an analog output through a serial communication
link.
Settings
Diagnostics
Actual signal Additional information
0120, 0121 Analog input values
1401 AI1/A2 signal loss
Alarm
AI1 LOSS / AI2 LOSS AI1/AI2 signal below limit 3021 AI1 FAULT LIMIT /
3022 AI2 FAULT LIMIT
Fault
AI1 LOSS / AI2 LOSS AI1/AI2 signal below limit 3021 AI1 FAULT LIMIT /
3022 AI2 FAULT LIMIT
PAR AI SCALE Incorrect AI signal scaling (1302 < 1301 or 1305 <
1304)
Parameter Additional information
Group 15 ANALOG OUTPUTS AO value selection and processing
Group 35 MOTOR TEMP MEAS AO in motor temperature measurement
Actual signal Additional information
0124 AO value
Fault
PAR AO SCALE Incorrect AO signal scaling (1503 < 1502)