Actual signals and parameters   217
0.5…50.0 Hz Frequency 1 = 0.1 Hz
3012 STALL TIME Defines the time for the stall function. See parameter 3010 
STALL FUNCTION.
20 s
10…400 s Time 1 = 1 s
3016 SUPPLY 
PHASE
Selects how the drive reacts to supply phase loss, ie when 
DC voltage ripple is excessive.
FAULT
FAULT The drive trips on fault SUPPLY PHASE and the motor 
coasts to stop when the DC voltage ripple exceeds 14% of 
the nominal DC voltage.
0
LIMIT/ALARM Drive output current is limited and alarm INPUT PHASE 
LOSS is generated when the DC voltage ripple exceeds 
14% of the nominal DC voltage.
There is a 10 s delay between the activation of the alarm 
and the output current limitation. The current is limited until 
the DC voltage ripple drops under the ripple limit.
1
ALARM The drive generates alarm INPUT PHASE LOSS when the 
DC ripple exceeds 14% of the nominal DC voltage.
2
3017 EARTH FAULT Selects how the drive reacts when an earth (ground) fault is 
detected in the motor or the motor cable. 
Note: Disabling earth (ground) fault may void the warranty.
ENABLE
DISABLE No action 0
ENABLE The drive trips on fault EARTH FAULT.1
3018 COMM FAULT 
FUNC
Selects how the drive reacts in a fieldbus communication 
break. The time delay is defined by parameter 3019 COMM 
FAULT TIME.
NOT SEL
NOT SEL Protection is inactive. 0
FAULT Protection is active. The drive trips on fault SERIAL 1 ERR 
and coasts to stop.
1
CONST SP 7 Protection is active. The drive generates alarm IO COMM 
and sets the speed to the value defined by parameter 1208 
CONST SPEED 7.
WARNING! Make sure that it is safe to continue 
operation in case of a communication break.
2
LAST SPEED Protection is active. The drive generates alarm IO COMM 
and freezes the speed to the level the drive was operating 
at. The speed is determined considering the average speed 
and time.
WARNING! Make sure that it is safe to continue 
operation in case of a communication break.
3
3019 COMM FAULT 
TIME
Defines the time delay for the fieldbus communication break 
supervision. See parameter 3018 COMM FAULT FUNC.
3.0 s
0.0…600.0 s Delay time 1 = 0.1 s
3021 AI1 FAULT 
LIMIT
Defines a fault level for analog input AI1. If parameter 3001 
AI<MIN FUNCTION is set to FAULT, the drive trips on fault 
AI1 LOSS when the analog input signal falls below the set 
level.
Do not set this limit below the level defined by parameter 
1301 MINIMUM A
I1.
0.0%
0.0…100.0% Value in percent of the full signal range 1 = 0.1%
All parameters
No. Name/Value Description Def/FbEq