112   Application macros
User macros
In addition to the standard application macros, it is possible to create two user 
macros. The user macro allows the user to save the parameter settings, including 
group 99 START-UP DATA, into the permanent memory and recall the data at a later 
time. The panel reference is also saved if the macro is saved and loaded in local 
control. The remote control setting is saved into the user macro, but the local control 
setting is not. 
The steps below show how to create and recall User macro 1. The procedure for the 
User macro 2 is identical, only the parameter 9902 values are different.
To create User macro 1:
• Adjust the parameters.
• Save the parameter settings to the permanent memory by changing parameter 
9902 to -1 (USER S1 SAVE). 
• Press   (Assistant control panel) or   (Basic control panel) to save. 
To recall User macro 1:
• Change parameter 9902 to 0 (USER S1 LOAD).
• Press   (Assistant control panel) or   (Basic control panel) to load.
The user macro can also be switched through digital inputs (see parameter 1605).
Note: User macro load restores the parameter settings, including group 99 START-
UP DATA. Check that the settings correspond to the motor used.
Hint: The user can for example switch the drive between two motors without having 
to adjust the motor parameters every time the motor is changed. The user needs only 
to adjust the settings once for each motor and then to save the data as two user 
macros. When the motor is changed, only the corresponding user macro needs to be 
loaded, and the drive is ready to operate.