Actual signals and parameters 165
Default values with different macros
When application macro is changed (9902 APPLIC MACRO), the software updates
the parameter values to their default values. The table below shows the parameter
default values for different macros. For other parameters, the default values are the
same for all macros. See the parameter list starting on page 177.
Index Name/
Selection
ABB
STAND
ARD
3-WIRE ALTERNA
TE
MOTOR
POT
HAND/
AUTO
PID
CONTROL
PFC
CONTROL
SPFC
CONTROL
AC500
MODBUS
9902 APPLIC
MACRO
1 =
ABB
STAND
ARD
2 =
3-WIRE
3=
ALTERNA
TE
4 =
MOTOR
POT
5 =
HAND/
AUTO
6 =
PID
CONTROL
7 =
PFC
CONTROL
15 =
SPFC
CONTROL
21 =
AC500
MODBUS
1001 EXT1
COMMANDS
2 =
DI1,2
4 =
DI1P,2P,
3
9 =
DI1F,2R
2 =
DI1,2
2 =
DI1,2
1 = DI1 1 = DI1 1 = DI1 10 =
COMM
1002 EXT2
COMMANDS
0 =
NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 =
NOT
SEL
21 =
DI5,4
20 = DI5 20 = DI5 20 = DI5 0 = NOT
SEL
1003 DIRECTION 3 =
REQU
EST
3 =
REQUES
T
3 =
REQUEST
3 =
REQUE
ST
3 =
REQUE
ST
1 =
FORWARD
1 =
FORWARD
1 =
FORWARD
3 =
REQUES
T
1102 EXT1/EXT2
SEL
0 =
EXT1
0 =
EXT1
0 = EXT1 0 =
EXT1
3 = DI3 2 = DI2 2 = DI2 2 = DI2 8 =
COMM
1103 REF1
SELECT
1 =
AI1
1 = AI1 1 = AI1 12 =
DI3U,4
D(NC)
1 = AI1 1 = AI1 1 = AI1 1 = AI1 8 =
COMM
1106 REF2
SELECT
2 =
AI2
2 = AI2 2 = AI2 2 = AI2 2 = AI2 19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
2 = AI2
1201 CONST
SPEED SEL
9 =
DI3,4
10 =
DI4,5
9 = DI3,4 5 = DI5 0
=NOT
SEL
3 = DI3 0 = NOT
SEL
0 = NOT
SEL
9 = DI3,4
1304 MINIMUM AI2 1.0% 1.0% 1.0% 1.0% 20.0% 20.0% 20.0% 20.0% 1.0%
1401 RELAY
OUTPUT 1
3 =
FAULT
(-1)
3 =
FAULT(-
1)
3 =
FAULT(-1)
3 =
FAULT(-
1)
3 =
FA
ULT(
-1)
3 =
FAULT(-1)
31 = PFC 31 = PFC 3 =
FAULT(-
1)
1601 RUN ENABLE 0 =
NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
4 = DI4 0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
1604 FAULT
RESET SEL
0 =
KEYP
AD
0 =
KEYPA
D
0 =
KEYPAD
0 =
KEYPA
D
0 =
KEYPA
D
0 =
KEYPAD
0 =
KEYPAD
0 =
KEYPAD
8 =
COMM
1805 DO SIGNAL 3 =
FAULT
(-1)
3 =
FAULT(-
1)
3 =
FAULT(-1)
3 =
FAULT(-
1)
3 =
FAULT(
-1)
3 =
FAULT(-1)
3 =
FAULT(-1)
31 = PFC 3 =
FAULT(-
1)
2008 MAXIMUM
FREQ
50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 52.0 Hz 52.0 Hz 50.0 Hz
2201 ACC/DEC 1/2
SEL
5 =
DI5
0 = NOT
SEL
5 = DI5 0 =
NOT
SEL
0 =
NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SE
L
2202 ACCELER
TIME 1
5.0s 5.0s 5.0s 5.0s 5.0s 5.0s 5.0s 30.0s 5.0s
2203 DECELER
TIME 1
5.0s 5.0s 5.0s 5.0s 5.0s 5.0s 5.0s 30.0s 5.0s
3018 COMM FAULT
FUNC
0 =
NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 =
NOT
SEL
0 =
NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
1 =
FAULT
3019 COMM FAULT
TIME
3.0s 3.0s 3.0s 3.0s 3.0s 3.0s 3.0s 10.0s 3.0s
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for ABB ACS310