Actual signals and parameters 177
All parameters
All parameters
No. Name/Value Description Def/FbEq
10 START/STOP/DIR The sources for external start, stop and direction control
1001 EXT1
COMMANDS
Defines the connections and the source for the start, stop
and direction commands for external control location 1
(EXT1).
DI1,2
NOT SEL No start, stop and direction command source 0
DI1 Start and stop through digital input DI1. 0 = stop, 1 = start.
Direction is fixed according to parameter 1003 DIRECTION
(setting REQUEST = FORWARD).
1
DI1,2 Start and stop through digital input DI1. 0 = stop, 1 = start.
Direction through digital input DI2. 0 = forward, 1 = reverse.
To control direction, parameter 1003 DIRECTION setting
must be REQUEST.
2
DI1P,2P Pulse start through digital input DI1. 0 -> 1: Start. (In order to
start the drive, digital input DI2 must be activated prior to the
pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction
of rotation is fixed according to parameter 1003 DIRECTION
(setting REQUEST = FORWARD).
Note: When the stop input (DI2) is deactivated (no input),
the control panel start and stop keys are disabled.
3
DI1P,2P,3 Pulse start through digital input DI1. 0 -> 1: Start. (In order to
start the drive, digital input DI2 must be activated prior to the
pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction
through digital input DI3. 0 = forward, 1 = reverse. To control
direction, parameter 1003 DIRECTION setting must be
REQUEST.
Note: When the stop input (DI2) is deactivated (no input),
the control panel start and stop keys are disabled.
4
DI1P,2P,3P Pulse start forward through digital input DI1. 0 -> 1: Start
forward. Pulse start reverse through digital input DI2. 0 -> 1:
Start reverse. (In order to start the drive, digital input DI3
must be activated prior to the pulse fed to DI1/DI2). Pulse
stop through digital input DI3. 1 -> 0: Stop. To control the
direction, parameter 1003 DIRECTION setting must be
REQUEST.
Note: When the stop input (DI3) is deactivated (no input),
the control panel start and stop keys are disabled.
5
KEYPAD Start, stop and direction commands through control panel
when EXT1 is active. To control the direction, parameter
1003 DIRECTION setting must be REQUEST.
8
DI1F,2R Start, stop and direction commands through digital inputs
DI1 and DI2.
Parameter 1003 DIRECTION setting must be
3(REQUEST).
9
DI1 DI2 Operation
00Stop
1 0 Start forward
0 1 Start reverse
11Stop