Parameters 123
Reserved Bit 5 of 34.01 Timed functions status.32
Supervision 1 Bit 0 of 32.01 Supervision status.33
Supervision 2 Bit 1 of 32.01 Supervision status.34
Supervision 3 Bit 2 of 32.01 Supervision status.35
Start delay Bit 13 of 06.17 Drive status word 2.39
RO/DIO control word
bit0
Bit 0 of 10.99 RO/DIO control word.40
RO/DIO control word
bit1
Bit 1 of 10.99 RO/DIO control word.41
RO/DIO control word
bit2
Bit 2 of 10.99 RO/DIO control word.42
11.07 DIO1 ON delay Defines the on (activation) delay for digital input/output
DIO1 (when used as a digital output or digital input).
0.00 s
0.0 3000.0 s Activation delay for DIO1. 10 = 1 s
11.08 DIO1 OFF delay Defines the deactivation delay for digital input/output DIO1
(when used as a digital output or digital input). See
parameter 11.07 DIO1 ON delay.
0.00 s
0.0 3000.0 s Deactivation delay for DIO1. 10 = 1 s
11.09 DIO2 function Selects whether DIO2 is used as a digital output or input,
or a frequency output. Note: DIOs cannot be used as
frequency inputs.
Digital output
Digital output DIO2 is used as a digital output. 0
Input DIO2 is used as a digital input. 1
Frequency output DIO2 is used as frequency output. 2
11.10 DIO2 output source Selects a drive signal to be connected to digital
input/output DIO2 when parameter 11.09 DIO2 function is
set to Digital output.
For the available selections, see parameter 11.0 6 DIO1
output source.
Ready run
11.11 DIO2 ON delay Defines the activation delay for digital input/output DIO2
(when used as a digital output or digital input).
0.00 s
0.0 300.0 s Activation delay for DIO2 10 = 1 s
11.12 DIO2 OFF delay Defines the deactivation delay for digital input/output DIO2
(when used as a digital output or digital input). See
parameter 11.11 DIO1 ON delay.
0.00 s
0.0 3000.0 s Deactivation delay for DIO2. 10 = 1 s
11.13 DI3 configuration Selects the type of digital input DI3: normal digital input or
frequency input.
Digital input
Digital input Digital input. See parameter 11.42 for more information. 0
Frequency input Frequency input. 1
11.17 DI4 configuration Selects the type of digital input DI4: normal digital input or
frequency input.
Digital input Digital input. 0
Frequency input Frequency input. 1
No. Name/Value Description Default
FbEq 16