270 Parameters
Silent mode Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the Refresh
settings selection of this parameter.
Note: If parameter 58.01 = [3] CANopen, this option is not
available.
2
58.07 Communication
diagnostics
Displays the status of the EFB communication.
This parameter is read-only.
Note that the name is only visible when the error is
present (bit value is 1).
Note: If parameter 58.01 = [3] CANopen, this parameter is
hidden.
-
0000h…FFFFh EFB communication status. 1 = 1
58.08 Received packets Displays a count of valid packets addressed to the drive.
During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
Note: If parameter 58.01 = [3] CANopen, this parameter is
hidden.
-
0…4294967295 Number of received packets addressed to the drive. 1 = 1
No. Name/Value Description Default
FbEq 16
Bit Name Description
0 Init failed 1 = EFB initialization failed
1 Addr config err 1 = Node address not allowed by protocol
2 Silent mode 1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3 Autobauding
4 Wiring error 1 = Errors detected (A/B wires possibly swapped)
5 Parity error 1 = Error detected: check parameters 58.04 and 58.05
6 Baud rate error 1 = Error detected: check parameters 58.05 and 58.04
7 No bus activity 1 = 0 bytes received during last 5 seconds
8 No packets 1 = 0 packets (addressed to any device) detected during last 5
seconds
9 Noise or addressing
error
1 = Errors detected (interference, or another device with the
same address on line)
10 Comm loss 1 = 0 packets addressed to the drive received within timeout
(58.16)
11 CW/Ref loss 1 = No control word or references received within timeout (58.16)
12 Not active Reserved
13 Protocol 1 Reserved
14 Protocol 2 Reserved
15 Internal error 1 = Internal errors detected