Parameters 271
58.09 Transmitted packets Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
Note: If parameter 58.01 = [3] CANopen, this parameter is
hidden.
-
0…4294967295 Number of transmitted packets. 1 = 1
58.10 All packets Displays a count of valid packets addressed to any device
on the bus. During normal operation, this number
increases constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
Note: If parameter 58.01 = [3] CANopen, this parameter is
hidden.
-
0…4294967295 Number of all received packets. 1 = 1
58.11 UART errors Displays a count of character errors received by the drive.
An increasing count indicates a configuration problem on
the bus.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
Note: If parameter 58.01 = [3] CANopen, this parameter is
hidden.
-
0…4294967295 Number of UART errors. 1 = 1
58.12 CRC errors Displays a count of packets with a CRC error received by
the drive. An increasing count indicates interference on
the bus.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
Note: If parameter 58.01 = [3] CANopen, this parameter,
is hidden.
-
0…4294967295 Number of CRC errors. 1 = 1
58.14 Communication loss
action
Selects how the drive reacts to an EFB communication
break. The drive does not trip if only reference is coming
from EFB and the communication is lost.
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06 Communication control (Refresh settings).
See also parameters 58.15 Communication loss mode
and 58.16 Communication loss time.
Fault
No No action taken (monitoring disabled).
For Modbus only.
0
No action No action taken (monitoring disabled).
For CANopen only.
0
Fault Drive trips on 6681 EFB comm loss. This occurs only if
control in the currently active control location is expected
from the EFB.
1
No. Name/Value Description Default