EasyManua.ls Logo

ABB ACS380 Series - Page 87

ABB ACS380 Series
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Program features 87
The internal brake choppers in the drive (in frames R0…R3) start conducting when
the DC link voltage reaches approximately 1.15 × U
DCmax
. 100% maximum pulse
width is reached at approximately 1.2 × U
DCmax
. (U
DCmax
is the DC voltage
corresponding to the maximum of the AC supply voltage range.) For information on
external brake choppers, refer to their documentation.
Note: Overvoltage control needs to be disabled for the chopper to operate.
Parameters
Parameters: 01.11 DC voltage, 30.30 Overvoltage control, group 43 Brake chopper.

Table of Contents

Other manuals for ABB ACS380 Series

Related product manuals