EasyManua.ls Logo

ABB ACS580-01 - Replacing the Main Cooling Fan, IP21 and IP55 (UL Type 1 and UL Type 12) Frames R5

ABB ACS580-01
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance and hardware diagnostics 147
Replacing the main cooling fan, IP21 and IP55 (UL Type 1 and UL
Type 12) frames R5…R8
WARNING! Obey the instructions in chapter Safety instructions on page 13.
Ignoring the instructions can cause physical injury or death, or damage to the
equipment.
1. Stop the drive and disconnect it from the power line. Wait for 5 minutes and then
make sure by measuring that there is no voltage. See section Precautions before
electrical work on page 16 before you start the work.
2. Remove the two mounting screws of the fan mounting plate at the bottom of the
drive.
3. Pull the fan mounting plate down from the side edge.
4. Unplug the fan power supply wires from the drive.
5. Lift the fan mounting plate off.
6. Remove the fan from the mounting plate.
7. Install the new fan in reverse order.
2
3
4
6

Table of Contents

Other manuals for ABB ACS580-01

Related product manuals