96 Electrical installation
Connecting the power cables
Connection diagram
1 For alternatives, see section Selecting the supply disconnecting device on page 65.
2 Use a separate grounding PE cable (2a) or a cable with a separate PE conductor (2b)
if the conductivity of the shield does not meet the requirements for the PE conductor
(see page 72).
3 360-degree grounding is recommended if shielded cable is used. Ground the other end
of the input cable shield or PE conductor at the distribution board.
4 360-degree grounding is required.
5 External brake resistor.
6 Use a separate grounding cable if the shield does not meet the requirements of
IEC 61439-1 (see page 72) and there is no symmetrically constructed grounding
conductor in the cable (see page 74).
7 du/dt or common mode filter (optional), see page 273.
Note:
If there is a symmetrically constructed grounding conductor on the motor cable in addition to
the conductive shield, connect the grounding conductor to the grounding terminal at the drive
and motor ends.
Do not use an asymmetrically constructed motor cable for motors above 30 kW (see page 72).
Connecting its fourth conductor at the motor end increases bearing currents and causes extra
wear.
L1 L2 L3
T1/U T2/V T3/W
UDC+
R+R-
L1 L2 L3(PE) (PE)PE
PE
U1
V1
W1
3 ~ M
1
2a
2b
3
5
6
4
3
ACS580-01
7