Technical data 161
NEMA ratings
Definitions
Type
ACS580
-01-
Input
rating
Max.
current
Output ratings
Max.
losses
Air
flow
Frame
size
North
American
type
Nominal use Heavy-duty use
I
1
I
max
I
LD
P
LD
I
Hd
P
Hd
ACS580
-01-
A A A hp A hp
W
ft
3
/min
3-phase U
N
= 480 V (440…480 V)
02A7-4 2.1 2.9 2.1 1.0 1.6 0.75 45 20 R1 02A1-4
03A4-4 3.0 3.8 3.0 1.5 2.1 1.0 55 20 R1 03A0-4
04A1-4 3.4 5.4 3.4 2.0 3.0 1.5 66 20 R1 03A5-4
05A7-4 4.8 6.1 4.8 3.0 3.4 2.0 84 20 R1 04A8-4
07A3-4 6.0 7.2 6.0 3.0 4.0 3.0 106 29 R1 06A0-4
09A5-4 7.6 8.6 7.6 5.0 4.8 3.0 133 29 R1 07A6-4
12A7-4 11.0 11.4 11.0 7.5 7.5 5.0 174 29 R1 012A-4
018A-4 14.0 19.8 14.0 10.0 11.0 7.5 228 75 R2 014A-4
026A-4 21.0 25.2 21.0 14.0 15.0 10.0 322 75 R2 023A-4
033A-4 27.0 37.8 27.0 20.0 21.0 15.0 430 105 R3 027A-4
039A-4 34.0 48.6 34.0 25.0 27.0 20.0 525 105 R3 034A-4
046A-4 40.0 61.2 44.0 30.0 34.0 25.0 619 105 R3 044A-4
062A-4 52 76 52 40 40 30 835 79 R4 052A-4
073A-4 65 104 65 50 52 40 1024 79 R4 065A-4
088A-4 77 122 77 60 65 50 1240 82 R5 078A-4
106A-4 96 148 96 75 77 60 1510 82 R5 096A-4
145A-4 124 178 124 100 96 75 1476 256 R6 124A-4
169A-4 156 247 156 125 124 100 1976 265 R7 156A-4
206A-4 180 287 180 150 156 125 2346 265 R7 180A-4
246A-4 240 350 240 200 180 150 3336 324 R8 240A-4
293A-4 260 418 260 200 240
1)
150 3936 324 R8 260A-4
363A-4 361 542 361 300 302 250 4836 677 R9 361A-4
430A-4 414 542 414 350 361
2)
300 6036 677 R9 414A-4
3AXD00000586715.xls J
U
N
Nominal voltage of the drive. For input voltage range, see section Electrical
power network specification on page 183.
I
1
Nominal input current (rms) at 40 °C (104 °F)
I
max
Maximum output current. Available for two seconds at start.
I
N
Nominal output current. Maximum continuous rms output current allowed (no
overload). This is indicated in the type designation label as output current I2.
P
N
Nominal power of the drive. Typical motor power (no overloading). The kilowatt
ratings apply to most IEC 4-pole motors. The horsepower ratings apply to most
NEMA 4-pole motors.
I
Ld
Maximum current with 110% overload, allowed for one minute every ten minutes
P
Ld
Typical motor power in light-duty use (110% overload)