172 Technical data
Circuit breakers
The table below lists MCB and MCCB circuit breakers that can be used with the drive.
Not allowed for US installation.
Type
ACS580
-01-
MCBs and MCCBs
ABB type Max.
short-
circuit
Tmax
frame XT
/ T class
Tmax
rating
Electronic
release
SACE ordering
code for breaker
and release unit
I
sc
kA A A A
3-phase U
N
= 400 or 480 V (380…415 V, 440…480 V)
02A7-4 S 203P-B/C/Z 10 20 N/A N/A N/A N/A
03A4-4
S 203P-B/C/Z 10 20 N/A N/A N/A N/A
04A1-4
S 203P-B/C/Z 10 20 N/A N/A N/A N/A
05A7-4
S 203P-B/C/Z 10 20 N/A N/A N/A N/A
07A3-4
S 203P-B/C/Z 10 20 N/A N/A N/A N/A
09A5-4
S 203P-B/C/Z 10 20 N/A N/A N/A N/A
12A7-4
S 203P-B/C/Z 16 20 N/A N/A N/A N/A
018A-4
S 203P-B/C/Z 20 20 N/A N/A N/A N/A
026A-4
S 203P-B/C/Z 25 20 N/A N/A N/A N/A
033A-4
S 203P-B/C/Z 32 12 N/A N/A N/A N/A
039A-4
S 203P-B/C/Z 40 12 N/A N/A N/A N/A
046A-4
S 203P-B/C/Z 50 12 N/A N/A N/A N/A
062A-4 S 803S-B/C 80 50 N/A N/A N/A N/A
073A-4 S 803S-B/C 80 50 N/A N/A N/A N/A
088A-4 S 803S-B/C 100 50 N/A N/A N/A N/A
106A-4 S 803S-B/C 125 50 N/A N/A N/A N/A
145A-4 XT4 L 250 Ekip LS/I
In=250 3p F F
65 XT4 250 250 1SDA068555R1
169A-4 XT4 L 250 Ekip LS/I
In=250 3p F F
65 XT4 250 250 1SDA068555R1
206A-4 T4 L 320 PR221DS-
LS/I In=320 3p F F
65 T4 320 320 1SDA054141R1
246A-4 T5 L 400 PR221DS-
LS/I In=400 3p F F
65 T5 400 400 1SDA054365R1
293A-4 T5 L 630 PR221DS-
LS/I In=630 3p F F
65 T5 630 630 1SDA054420R1
363A-4 T5 L 630 PR221DS-
LS/I In=630 3p F F
65 T5 630 630 1SDA054420R1
430A-4 T5 L 630 PR221DS-
LS/I In=630 3p F F
65 T5 630 630 1SDA054420R1
3AXD00000586715.xls J