182 Technical data
Terminal and lead-through data for the control cables
IEC
Control cable lead-throughs, wire sizes and tightening torques (T) are given below.
US
Control cable lead-throughs, wire sizes and tightening torques (T) are given below.
Frame
size
Cable lead-
throughs
Control cable entries and terminal sizes
Holes Max
cable
size
+24V, DCOM, DGND, EXT. 24V
terminals
DI, AI/O, AGND, RO, STO
terminals
Wire size T Wire size T
pcs mm mm
2
N·m mm
2
N·m
R1 3 17 0.2…2.5 0.5…0.6 0.14…1.5 0.5…0.6
R2 3 17 0.2…2.5 0.5…0.6 0.14…1.5 0.5…0.6
R3 3 17 0.2…2.5 0.5…0.6 0.14…1.5 0.5…0.6
R4 4 17 0.2…2.5 0.5…0.6 0.14…1.5 0.5…0.6
R5 3 17 0.2…2.5 0.5…0.6 0.14…1.5 0.5…0.6
R6 4 17 0.14…2.5 0.5…0.6 0.14…2.5 0.5…0.6
R7 4 17 0.14…2.5 0.5…0.6 0.14…2.5 0.5…0.6
R8 4 17 0.14…2.5 0.5…0.6 0.14…2.5 0.5…0.6
R9 4 17 0.14…2.5 0.5…0.6 0.14…2.5 0.5…0.6
3AXD00000586715.xls J