Technical data 177
Cooling air flow and heat dissipation for flange mounting (option
+C135)
Type
ACS580
-01-
Heat dissipation
(option +135)
Air flow
(option +135)
Frame
size
Heatsink Front Heatsink Front
W W m
3
/h ft
3
/min m
3
/h ft
3
/min
3-phase U
N
= 400 or 480 V (380…415 V, 440…480 V)
145A-4 1251 189 435 256 52 31 R6
169A-4 1701 239 450 265 75 44 R7
206A-4 2034 276 450 265 75 44 R7
246A-4 2925 375 550 324 120 71 R8
293A-4 3465 435 550 324 120 71 R8
363A-4 4275 525 1150 677 170 100 R9
430A-4 5355 645 1150 677 170 100 R9
3AXD00000586715.xls J