176 Technical data
Losses, cooling data and noise
The air flow direction is from bottom to top.
Cooling air flow, heat dissipation and noise for stand-alone drives
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O, options and panel not in use) and
maximum load (all digital inputs and relays in the ON state, and the panel, fieldbus
and fan in use). The total heat dissipation is the sum of the heat dissipation in the
main and control circuits. Use the maximum heat dissipation when designing cabinet
or electrical room cooling needs.
Type
ACS580
-01-
Heat dissipation Air flow Noise Frame
size
Main circuit
at rated
I
1N
at I
N
Control
circuit
minimum
Control
circuit
maximum
Main and
control boards
maximum
W W W W m
3
/h ft
3
/min dB(A)
3-phase U
N
= 400 or 480 V (380…415 V, 440…480 V)
02A7-4 20 3.5 25 45 34 20 55 R1
03A4-4 30 3.5 25 55 34 20 55 R1
04A1-4 41 3.5 25 66 34 20 55 R1
05A7-4 59 3.5 25 84 34 20 55 R1
07A3-4 81 3.5 25 106 50 29 55 R1
09A5-4 108 3.5 25 133 50 29 55 R1
12A7-4 149 3.5 25 174 50 29 55 R1
018A-4 203 3.5 25 228 128 75 66 R2
026A-4 297 3.5 25 322 128 75 66 R2
033A-4 405 3.5 25 430 116 68 70 R3
039A-4 500 3.5 25 525 116 68 70 R3
046A-4 594 3.5 25 619 116 68 70 R3
062A-4 810 3.5 25 835 134 79 69 R4
073A-4 999 3.5 25 1024 134 79 69 R4
088A-4 1215 3.5 25 1240 139 82 63 R5
106A-4 1485 3.5 25 1510 139 82 63 R5
145A-4 1440 4.1 36 1476 435 256 67 R6
169A-4 1940 4.1 36 1976 450 265 67 R7
206A-4 2310 4.1 36 2346 450 265 67 R7
246A-4 3300 4.1 36 3336 550 324 65 R8
293A-4 3900 4.1 36 3936 550 324 65 R8
363A-4 4800 4.1 36 4836 1150 677 68 R9
430A-4 6000 4.1 36 6036 1150 677 68 R9
3AXD00000586715.xls J