76 Planning the electrical installation
Shielded power cables are available from the following suppliers:
• Belden
• LAPPKABEL (ÖLFLEX)
• Pirelli.
Selecting the control cables
Shielding
All control cables must be shielded.
Use a double-shielded twisted pair cable (figure a below) for analog signals. Employ
one individually shielded pair for each signal. Do not use common return for different
analog signals.
A double-shielded cable is the best alternative for low-voltage digital signals but
single-shielded (b) twisted pair cable is also acceptable.
Signals in separate cables
Run analog and digital signals in separate, shielded cables.
Do not mix 24 V AC/DC and 115/230 V AC signals in the same cable.
Signals allowed to be run in the same cable
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in
the same cables as digital input signals. The relay-controlled signals should be run as
twisted pairs.
Relay cable
The cable type with braided metallic screen (for example ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by the manufacturer.
Control panel cable
In remote use, the cable connecting the control panel to the drive must not exceed
100 m (330 ft). If multiple drives are connected, the total length of the panel bus must
not exceed 100 m (330 ft).