Optional I/O extension modules 261
Examples are given below.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate
the reverse direction of rotation of the motor with a one-second delay.
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module indicate
the reverse direction of rotation of the motor with a one-second delay.
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module indicate
the motor speed 0... 1500 rpm with a frequency range of 0...10000 Hz.
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
Parameter Setting
15.07 RO4 source Reverse
15.08 RO4 ON delay 1 s
15.09 RO4 OFF delay 1 s
Parameter Setting
15.22 DO1 configuration Digital output
15.23 DO1 source Reverse
15.24 DO1 ON delay 1 s
15.25 DO1 OFF delay 1 s
Parameter Setting
15.22 DO1 configuration Frequency output
15.33 Freq out 1 source 01.01
15.34 Freq out 1 src min 0
15.35 Freq out 1 src max 1500.00
15.36 Freq out 1 at src min 1000 Hz
15.37 Freq out 1 at src max 10000 Hz
Color Description
Green The extension module is powered up.