Technical data 169
gG fuses
Check on the fuse time-current curve to ensure the operating time of the fuse is
below 0.5 seconds. Obey the local regulations.
Type
ACS580
-01-
Min.
short-
circuit
current
1)
Input
current
gG (IEC 60269) North
American
type
ACS580
-01-
Nominal
current
I
2
t Voltage
rating
ABB type IEC
60269
size
A A A A
2
s V
3-phase U
N
= 400 or 480 V (380…415 V, 440…480 V)
02A7-4 32 2.6 4 55 500 OFAF000H4 000 02A1-4
03A4-4 48 3.3 6 110 500 OFAF000H6 000 03A0-4
04A1-4 48 4.0 6 110 500 OFAF000H6 000 03A5-4
05A7-4 80 5.6 10 360 500 OFAF000H10 000 04A8-4
07A3-4 80 7.2 10 360 500 OFAF000H10 000 06A0-4
09A5-4 128 9.4 16 740 500 OFAF000H16 000 07A6-4
12A7-4 128 12.6 16 740 500 OFAF000H16 000 012A-4
018A-4 200 17.0 25 2500 500 OFAF000H25 000 014A-4
026A-4 256 25.0 32 4000 500 OFAF000H32 000 023A-4
033A-4 320 32.0 40 7700 500 OFAF000H40 000 027A-4
039A-4 400 38.0 50 16000 500 OFAF000H50 000 034A-4
046A-4 500 45.0 63 20100 500 OFAF000H63 000 044A-4
062A-4 800 62 80 37500 500 OFAF000H80 000 052A-4
073A-4 1000 73 100 65000 500 OFAF000H100 000 065A-4
088A-4 1000 88 100 65000 500 OFAF000H100 000 078A-4
106A-4 1300 106 125 103000 500 OFAF00H125 00 096A-4
145A-4 1700 145 160 185000 500 OFAF00H160 00 124A-4
169A-4 3300 169 250 600000 500 OFAF0H250 0 156A-4
206A-4 5500 206 315 710000 500 OFAF1H315 1 180A-4
246A-4 6400 246 355 920000 500 OFAF1H355 1 240A-4
293A-4 7800 293 425 1300000 500 OFAF2H425 2 260A-4
363A-4 9400 363 500 2000000 500 OFAF2H500 2 361A-4
430A-4 10200 430 630 2800000 500 OFAF3H630 3 414A-4
3AXD00000586715.xls J
1)
Minimum short-circuit current of the installation