Technical data 175
See the figures in section Checking the installation site on page 44.
Frame
size
Free space, IP21 (UL Type 1) and IP55 (UL Type 12)
Vertical mounting
stand alone
Vertical mounting
side by side
Above Below Beside Above Below Between
mm in mm in mm in mm in mm in mm in
R1 200 7.87 30 1.18 150 5.91 200 7.87 300 7.87 0 0
R2 200 7.87 30 1.18 150 5.91 200 7.87 300 7.87 0 0
R3 200 7.87 200 7.87 200 7.87 200 7.87 200 7.87 0 0
R4 53 2.09 200 7.87 150 5.91 200 7.87 200 7.87 0 0
R5 100 3.94 200 7.87 150 5.91 200 7.87 200 7.87 0 0
R6 155 6.10 300 11.8 150 5.91 200 7.87 300 11.8 0 0
R7 155 6.10 300 11.8 150 5.91 200 7.87 300 11.8 0 0
R8 155 6.10 300 11.8 150 5.91 200 7.87 300 11.8 0 0
R9 200 7.87 300 11.8 150 5.91 200 7.87 300 11.8 0 0
3AXD00000586715.xls J
Frame
size
Free space,
IP21 (UL Type 1) and IP55 (UL Type 12)
Horizontal mounting
Above
1)
Below
1)
Between
1)
mm in mm in mm in
R1 200 7.87 30 1.18 30/200 1.18/7.87
R2 200 7.87 30 1.18 30/200 1.18/7.87
R3 200 7.87 30 1.18 30/200 1.18/7.87
3AXD00000586715.xls J
1)
For definition, see the figure on page 45.