Resistor braking 225
The table shows reference resistor types for the maximum braking power.
WARNING! Do not use a brake resistor with a resistance below the minimum
value specified for the particular drive. The drive and the internal chopper are
not able to handle the overcurrent caused by the low resistance.
Type
ACS580
-01-
R
min
R
max
P
BRmax
Reference resistor types
ohm ohm kW hp Danotherm
3-phase U
N
= 400 or 480 V (380…415 V, 440…480 V)
02A7-4 52 864 0.6 0.8 CBH 360 C T 406 210R
03A4-4 52 582 0.9 1.2 CBH 360 C T 406 210R
04A1-4 52 392 1.4 1.9 CBH 360 C T 406 210R
05A7-4 52 279 2.0 2.7 CBH 360 C T 406 210R
07A3-4 52 191 2.9 3.9 CBR-V 330 D T 406 78R UL
09A5-4 52 140 3.9 5.2 CBR-V 330 D T 406 78R UL
12A7-4 52 104 5.3 7.1 CBR-V 330 D T 406 78R UL
018A-4 31 75 7.3 9.8 CBR-V 560 D HT 406 39R UL
026A-4 22 52 10 13.6 CBR-V 560 D HT 406 39R UL
033A-4 16 37 15 20.1 CBT-H 560 D HT 406 19R
039A-4 10 27 20 26.8 CBT-H 760 D HT 406 16R
046A-4 10 22 25 33.5 CBT-H 760 D HT 406 16R
3AXD10000395897.xls E
Symbols
R
min
= minimum allowed brake resistor that can be connected to the brake chopper
R
max
= maximum allowed brake resistor that allows P
BRmax
P
BRmax
= maximum braking capacity of the drive, must exceed the desired braking power.