Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1Constant 1.True
2Bit 0 of 10.21 RO status (page 214).RO1
See Terms and abbreviations (page 169).Other [bit]
On-time 1 exceeded
/ uint32
Selects the optional warning message for on-time timer
1.
On-time 1 warn
message
33.14
0A886 On-Time 1. The message text can be edited on
the control panel by choosing Menu Settings Edit
texts.
On-time 1 exceeded
6A88C Device clean.Clean device
7A890 Additional cooling fan.Maintain additional
cooling fan
8A88E Cabinet fan.Maintain cabinet fan
9A88D DC capacitor.Maintain DC
capacitors
10A880 Motor bearing.Maintain motor
bearing
- / uint32Displays the actual present value of on-time timer 2.
The timer runs whenever the signal selected by
parameter 33.23 On-time 2 source is on.
When the timer exceeds the limit set by 33.21 On-time
2 warn limit, bit 1 of 33.1 Counter status is set to 1. The
warning specified by 33.24 On-time 2 warn message is
also given if enabled by 33.22 On-time 2 function.
The timer can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
On-time 2 actual33.20
- / -Actual present value of on-time timer 2.0...4294967295 s
- / uint32Sets the warning limit for on-time timer 2.On-time 2 warn limit33.21
- / -Warning limit for on-time timer 2.0...4294967295 s
- / uint16Configures on-time timer 2.On-time 2 function33.22
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 1 of 33.1) switches to 1 for one
second. The warning (if enabled) stays active for at
least 10 seconds.
1 = Saturate: When the limit is reached, the counter
status (bit 1 of 33.1) switches to 1, and remains so until
33.20 is reset. The warning (if enabled) also stays active
until 33.20 is reset.
Counter modeb0
0 = Disable: No warning is given when the limit is
reached
1 = Enable: A warning (see 33.24) is given when the limit
is reached
Warning enableb1
Reservedb2…15
1 = 10000h…FFFFh
False / uint32Selects the signal to be monitored by on-time timer 2.On-time 2 source33.23
0Constant 0 (timer disabled).False
390 Parameters