Parameter Values (Range) Unit Step Default Description
Max forward angle 0...90 deg 1 80 Maximum phase angle in
forward direction
Max reverse angle 0...90 deg 1 80 Maximum phase angle in
reverse direction
Min forward angle 0...90 deg 1 80 Minimum phase angle in
forward direction
Min reverse angle 0...90 deg 1 80 Minimum phase angle in
reverse direction
Table 278: DPHHPDOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve
type
Voltage Mem time 0...3000 ms 1 40 Voltage memory time
Pol quantity 1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
5=Cross pol Reference quantity used
to determine fault direc-
tion
Table 279: DPHHPDOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for customer
programmable curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for customer
programmable curve
Curve parameter C 0.02...2.00 1 2.00 Parameter C for customer
programmable curve
Curve parameter D 0.46...30.00 1 29.10 Parameter D for customer
programmable curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for customer
programmable curve
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases re-
quired for operate activa-
tion
Table 280: DPHHPDOC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum operate
time
20...60000 ms 1 20 Minimum operate time for
IDMT curves
Table continues on the next page
Protection functions 1MRS758755 C
260 REC615 & RER615