Parameter Values (Range) Unit Step Default Description
Allow Non Dir 0=False
1=True
0=False Allows prot activation as
non-dir when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used measure-
ment mode
Min operate cur-
rent
0.01...1.00 xIn 0.01 0.01 Minimum operating cur-
rent
Min operate volt-
age
0.01...1.00 xUn 0.01 0.01 Minimum operating volt-
age
4.1.2.10 Monitored data
Table 281: FDPHLPDOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
FAULT_DIR Enum
0=unknown
1=forward
2=backward
3=both
Detected fault
direction
DIRECTION Enum
0=unknown
1=forward
2=backward
3=both
Direction infor-
mation
DIR_A Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase
A
DIR_B Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase
B
DIR_C Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase
C
Table continues on the next page
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
261