EasyManua.ls Logo

ABB Relion REC615 - Page 327

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
15=IEC Def. Time
17=Programmable
15=IEC Def. Time Selection of time
delay curve type
Operate delay time 40...200000 ms 10 40 Operate delay time
Characteristic an-
gle
-179...180 deg 1 -90 Characteristic an-
gle
Max forward angle 0...180 deg 1 80 Maximum phase
angle in forward di-
rection
Max reverse angle 0...180 deg 1 80 Maximum phase
angle in reverse di-
rection
Min forward angle 0...180 deg 1 80 Minimum phase an-
gle in forward di-
rection
Min reverse angle 0...180 deg 1 80 Minimum phase an-
gle in reverse direc-
tion
Voltage start value 0.010...1.000 xUn 0.001 0.010 Voltage start value
Table 361: DEFHPDEF Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset
curve type
Operation mode 1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle Operation criteria
Enable voltage limit 0=False
1=True
1=True Enable voltage limit
Table 362: DEFHPDEF Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 1 2.00 Parameter C for
customer program-
mable curve
Table continues on the next page
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
327

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals