Parameter Values (Range) Unit Step Default Description
Curve parameter D 0.46...30.00 1 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for
customer program-
mable curve
Table 363: DEFHPDEF Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum operate
time
40...60000 ms 1 40 Minimum operate
time for IDMT
curves
Allow Non Dir 0=False
1=True
0=False Allows prot activa-
tion as non-dir
when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Min operate current 0.005...1.000 xIn 0.001 0.005 Minimum operating
current
Min operate volt-
age
0.01...1.00 xUn 0.01 0.01 Minimum operating
voltage
Correction angle 0.0...10.0 deg 0.1 0.0 Angle correction
Pol reversal 0=False
1=True
0=False Rotate polarizing
quantity
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used
Io signal
Uo signal Sel 1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used
Uo signal
Pol quantity 3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt. Reference quantity
used to determine
fault direction
4.2.2.12 Monitored data
Table 364: DEFLPDEF Monitored data
Name
Type Values (Range) Unit Description
FAULT_DIR Enum
0=unknown
1=forward
2=backward
Detected fault
direction
Table continues on the next page
Protection functions 1MRS758755 C
328 REC615 & RER615
Technical Manual