EasyManuals Logo

Allen-Bradley SMC-50 User Manual

Allen-Bradley SMC-50
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #163 background imageLoading...
Page #163 background image
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 163
Troubleshooting Chapter 9
Table 61 - Motor Stops While Running
Display Possible Cause Possible Solutions
Fault displayed See fault description See addressing fault conditions
HIM display is blank
•Failed HIM
Control voltage is absent
Failed control module
HIM connection is loose
Replace HIM
Check control wiring and correct if necessary
Replace control module
Check HIM connection
Stopped
0.0 Amps
•Pilot devices
Failed control module
Check control wiring and correct if necessary
Replace control module
Starting
One or more power phases are missing
Failed control module
Check power system
Replace control module
Table 62 - Miscellaneous Situations
Display Possible Causes Possible Solutions
Motor current and voltage fluctuates with
steady load
Motor
Erratic Load
Verity type of motor as a standard
squirrel cage induction motor
Check load conditions
Erratic operation Loose connections Shut off all power to controller and
check for loose connections
Accelerates too fast Starting time
•Initial torque
Current limit setting
•Kickstart
Increase starting time
Lower initial torque setting
Decrease current limit setting
Lower kickstart time or turn off
Accelerates too slow Starting time
•Initial torque
Current limit setting
•Kickstart
Decrease starting time
Increase initial torque setting
Increase current limit setting
Increase kickstart time or turn off
Motor stops too quickly with Soft Stop
option
Time setting Verify the programmed stopping time
and correct if necessary
Motor stops too slowly with Soft Stop
option
Stopping time setting
Misapplication
Verify the programmed stopping time
and correct if necessary
The Soft Stop option is intended to
extend the stopping time for loads that
stop suddenly when power is removed
from the motor.
Fluid surges with pumps still occur with
the Soft Stop option
Misapplication Soft Stop ramps voltage down over a set
period of time. In the case of pumps, the
voltage may drop too rapidly to prevent
surges. A closed loop system such as
Pump Control would be more
appropriately suited.
Motor overheats Overload
Blocked ventilation
Allow motor to cool and reduce load.
Remove blockage and ensure motor is
being adequately cooled.
Motor short circuit Winding fault Identify fault and correct
Check for shorted SCR; replace if
necessary
Ensure power terminals are secure
Motor coasts when option stop is
programmed
Option not programmed
Current loop power supply not active
Incorrect control logic
Bypass contactor set for delayed drop-
out
Verify the option parameter settings
and correct if necessary
Verify current loop power supply
Verify connections to module terminals
16 and 17
Verify that the Bypass Contactor is
configured for <100ms drop-out time.
For relay control, the FDO version
contactor is required; for IntelliVAC
control, set Drop-out time to 50 ms (no
PFCC) or 75 ms (if PFCC contactor in
same controller). For IntelliVAC settings,
refer to Chapter 4 of 1503-UM053
.

Table of Contents

Other manuals for Allen-Bradley SMC-50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SMC-50 and is the answer not in the manual?

Allen-Bradley SMC-50 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSMC-50
CategoryController
LanguageEnglish

Related product manuals