218 Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A Parameter Information
215 Phase Shift 100 -360/360 0 Timing parameters used in speed measurement algorithms.
These parameters are not typically modified and it is
recommended that RA Technical Support be contacted for
assistance before attempting to do so.
R/W
216 Board Temp
o
C -25/100 20 Displays the internal temperature of the SMC control module. R
217 Exp 7 Config 0/5 0 [None]
Input/Output
Analog I/O
(future)
GFCT/PTC/CT
DIP Switch
Seq Start
(future)
Displays the type of expansion board plugged into Expansion
Port 7.
R
218 Exp 8 Config 0/5 0 [None]
Input/Output
Analog I/O
(future)
GFCT/PTC/CT
DIP Switch
Seq Start
(future)
Displays the type of expansion board plugged into Expansion
Port 8.
R
219 Exp 9 Config 0/5 0 [None]
Input/Output
Analog I/O
(future)
GFCT/PTC/CT
DIP Switch
Seq Start
(future)
Displays the type of expansion board plugged into Expansion
Port 9.
R
224 Line Frequency Hz 0/100 0 Displays the line frequency of the three phase voltage applied
to the SMC-50 at terminals L1, L2, and L3.
R
225 Freq High F Dly Secs 0.1/99 0.1 Allows the user to configure the time period that the supplied
line voltage frequency must exceed Freq High F Lvl parameter
value before causing a Freq High fault. The Freq High bit must
be set in the Starter Fault En parameter for the fault to activate.
R
226 Freq High A Dly Secs 0.1/99 0.1 Allows the user to configure the time period that the supplied
line voltage frequency must exceed Freq High A Lvl parameter
value before causing a Freq High alarm. The Freq High bit must
be set in the Starter Alarm parameter for the fault to activate.
R
227 Freq Low F Dly Secs 0.1/99 0.1 Allows the user to configure the time period that the supplied
line voltage frequency must drop below Freq Low F Lvl
parameter value before causing a Freq Low fault. The Freq Low
bit must be set in the Starter Fault En parameter for the fault to
activate.
R
Table 66 - SMC -50 Parameter List (Continued)
Number Name Unit Min/Max Default Enum Text Description R/W