Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 219
Parameter Information Appendix A
228 Freq Low A Dly Secs 0.1/99 0.1 Allows the user to configure the time period that the supplied
line voltage frequency must drop below Freq Low A Lvl
parameter value before causing a Freq Low alarm. The Freq Low
bit must be set in the Starter Alarm parameter for the fault to
activate.
R
229 Parameter Mgmt 0/1 0 [Ready]
Factory Default
Allows the user to force all the Control Module parameters to
default values. This has no impact on any option module(s)
installed. Each Option module has its own associated Parameter
Mgmt parameter:
[Ready]
: Waiting for command to set factory defaults
Factory Default: Command for SMC to set all Control Module
Writable Parameters to factory default values. This command
does not impact Option Module parameters.
R/W
230 Motor Fault En Bit Value 0/1 [Overload]
Underload
MWatts Over
Mwatts Under
+MVAR Over
+MVAR Under
-MVAR Over
-MVAR Under
MVA Under
MVA Over
Curr Imbal
Jam
[Stall]
Starts/Hr
PM Hours
PM Starts
[Power Qual]
[Open Load]
THD I
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor
Overcurrent EN
Allows the user to enable Motor related faults that can be
detected by the SMC-50.
0 = Fault Disabled
1 = Fault Enabled
[Default]
R/W
Table 66 - SMC -50 Parameter List (Continued)