220 Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A Parameter Information
231 Motor Alarm En Bit Value 0/1 Overload
Underload
MWatts Over
Mwatts Under
+MVAR Over
+MVAR Under
-MVAR Over
-MVAR Under
MVA Under
MVA Over
Curr Imbal
Jam
Stall
Starts/Hr
PM Hours
PM Starts
Power Qual
Open Load
THD I
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor
Allows the user to enable Motor related alarms that can be
detected by the SMC-50.
0 = Fault Disabled
1 = Fault Enabled
[All Disabled as Default]
R/W
232 +MVAR Ov F Lvl MVAR 0/1000 0.000 Allows the user to enter a value for the Consumed Reactive
Power Over Fault Level (+MVAR Ov F Lvl). If the current actual
+MVAR value is greater than the +MVAR OV F Lvl for a time
period greater than that defined by +MVAR Ov F Dly, a +MVAR
Ov Fault will be signaled.
R/W
233 +MVAR Ov F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the +MVAR Over Fault
delay. If the current actual value of Consumed Reactive Power
(+MVAR) is greater than the +MVAR OV F Lvl for a time period
greater than that defined by +MVAR Ov F Dly, a +MVAR Ov
Fault will be signaled
R/W
234 +MVAR Ov A Lvl MVAR 0/1000 0.000 Allows the user to enter a value for the Consumed Reactive
Power Over Alarm Level (+MVAR OV A Lvl). If the current actual
+MVAR value is greater than the +MVAR OV A Lvl for a time
period greater than that defined by +MVAR Ov A Dly, a +MVAR
Ov Alarm will be signaled.
R/W
235 +MVAR Ov A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the +MVAR Over Alarm
Delay (+MVAR Ov A Dly). If the current actual value of
Consumed Reactive Power (+MVAR) is greater than the +MVAR
Ov A Level for a time period greater than that defined by
+MVAR Ov A Dly, a +MVAR Ov Alarm will be signaled.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number Name Unit Min/Max Default Enum Text Description R/W