Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 221
Parameter Information Appendix A
236 +MVAR Un F Lvl MVAR 0/1000 0.000 Allows the user to enter a value for the Consumed Reactive
Power Under Fault Level (+MVAR Un F Lvl). If the current actual
+MVAR value is less than the +MVAR Un F Level for a time
period greater than that defined by +MVAR Un F Dly, a +MVAR
Un Fault will be signaled.
R/W
237 +MVAR Un F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the +MVAR Under
Fault delay. If the Consumed Reactive Power (+MVAR) is less
than the +MVAR Un F Level for a time period greater than that
defined by +MVAR Un F Dly, a +MVAR Un Fault will be signaled.
R/W
238 +MVAR Un A Lvl MVAR 0/1000 0.000 Allows the user to enter a value for the Consumed Reactive
Power Under Alarm Level (+MVAR Un A Lvl). If the current
actual value of Consumed Reactive Power (+MVAR) is less than
the +MVAR Un A Level for a time period greater than that
defined by +MVAR Un A Dly a +MVAR Un Alarm will be
signaled.
R/W
239 +MVAR Un A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the +MVAR Under
Alarm Delay (+MVAR Un A Dly). If the current actual value of
Consumed Reactive Power (+MVAR) is less than the +MVAR Un
A Level for a time period greater than that defined by +MVAR
Un A Dly, a +MVAR Un Alarm will be signaled.
R/W
240 MVA Ov F Lvl MVA 0/1000 0.000 Allows the user to enter a value for the MVA Over Fault Level
(MVA Ov F Lvl). If the current actual value of Apparent Power
(MVA) is greater than the MVA Ov F Lvl for a time period greater
than that defined by MVA Ov F Dly, a MVA Ov Fault will be
signaled.
R/W
241 MVA Ov F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Apparent Power
Over Fault Delay (MVA Ov F Dly). If the current actual value of
Apparent Power (MVA) is greater than the MVA Ov F Lvl for a
time period greater than that defined by MVA Ov F Dly, a MVA
Ov Fault will be signaled.
R/W
242 MVA Ov A Lvl MVA 0/1000 0.00 Allows the user to enter a value for the MVA Over Alarm Level
(MVA Ov A Lvl). If the current actual value of the Apparent
Power (MVA) is greater than the MVA Ov A Lvl for a time period
greater than that defined by MVA Ov A Dly, a MVA Ov Alarm will
be signaled.
R/W
243 MVA Ov A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Apparent Power
Over Alarm Delay (MVA Ov A Dly). If the current actual value of
the Apparent Power (MVA) is greater than the MVA Ov A Lvl for
a time period greater than that defined by MVA Ov A Dly, a MVA
Ov Alarm will be signaled.
R/W
244 MVA Un F Lvl MVA 0/1000 0.00 Allows the user to enter a value for the MVA Under Fault Level
(MVA Un F Lvl). If the current actual value of the Apparent
Power (MVA) is less than the MVA Un F Lvl for a time period
greater than that defined by MVA Un F Dly, a MVA Un Fault will
be signaled.
R/W
245 MVA Un F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Apparent Power
Under Fault Delay (MVA Un F Dly). If the current actual value of
the Apparent Power (MVA) is less than the MVA Un F Lvl for a
time period greater than that defined by MVA Un F Dly, a MVA
Un Fault will be signaled.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number Name Unit Min/Max Default Enum Text Description R/W